Smiths Products  
 
 
Industrial Water Chiller
Technical Characteristics
Digital electronic control,temperature control accuracy ±0.1℃
Precisely control machining fluid temperature.
Rust free water circulation system.
Multiple safety devices.
Cooling water tower free.
 
LS
R
380
BX
H
K
(G)
/
a
1
2
3
4
5
6
7
/
8
1
LS DVT precision water chiller for laser
2
R  with heating function
3
rated cooling capacity=nominal rate×100, unit: W
4
B with water pump;X with water tank
5

H:with high lift water pump(max.55m);L:with low lift water pump (max.40m)

6
K with flow switch signal output
7
G)factory setting is fixed temperature control mode;(T):factory setting is tracing temperature control mode
8
Special order code

 

High power laser cutter

 

Machine tools
 Machining centers
Main Technical Parameters    
Item/Type
Unit
LS-50BX(G)
LS-190BX(G)
LS-270BX(G)
LS-380BX(G)
LS-540BX(G)
LS-750BX(G)
LS-1000BX(G)
Cooling capacity
KW
5
19
27
38
54
75
100
Water inlet
24
20
20
20
20
20
20
Water outlet
21
15
15
15
15
15
15
Glyco
25
25
25
25
25
25
25
Power supply
V/Ph/Hz
230/1/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Power input
KW
2.3
7.5
10.8
16.8
21.5
33.6
38
Rated current
A
10.5
13
19.1
26
37.8
52
73.8
Water flow
m3/h
1.44
3.61
5.13
7.22
10.26

14.25

19
Pump lift
bar
1.5
3
3
3
3
3
3
Water tank
L
25
110
160
220
160
220
290
Refrigerant
 
R407C
Refrigerant charge
Kg
1.7
6.8
6.6
7.7
6.6
5.8
7.4
Dimensions
L
mm
760
1100
1200
1350
1500
1500
1650
W
mm
600
750
700
890
870
1300
1500
H
mm
820
1315
1360
1620
1670
1790
1800
Water connection
Inch
1/2“
1”
1 1/4”
1 1/2“
2”
2 1/2“
2 1/2”
Net weight
Kg
93.5
358
326
401
512
680
830
Noise
(5 meters off)
dB
56
60
62
64
64
66
66
Ingress protection
 
IP20
IP55
IP55
IP55
IP55
IP55
IP55